Sika® Unitherm® Steel S
1-component, solvent-based fire protection coating for steel components in the interior of buildings. Forms a heat insulating layer under the influence of fire and improves the fire resistance of steel parts.
- Quick-drying fire protection system
- Profile-following coating with low coating
- Excellent also for highly articulated components
- No static load
- Easy to process
- Flexible color design possible with coating varnish, color shades in RAL, DB, others available
Usage
- Increasing the fire resistance of steel beams, columns and trusses indoors (including open halls). Excluded are lightweight steel construction and components that are constantly exposed to constant moisture, frequent and prolonged periods of very high humidity or highly aggressive gases. For critical loads, e.g. if frequent condensate formation or heating of surfaces (> +45 °C), special measures must be taken if necessary.
- Quick drying and therefore also suitable for the factory application.
- Coatings can be dispensed with in permanently dry rooms.
Advantages
- Quick-drying fire protection system
- Profile-following coating with low coating
- Excellent also for highly articulated components
- No static load
- Easy to process
- Flexible color design possible with coating varnish, color shades in RAL, DB, others available
Packaging
25 kg
Colour
White
Product Details
APPROVALS / STANDARDS
- Declaration of Performance (DoP) No. 020604000030000013: CE marking in accordance with the requirements of standard EN 13381-8: 2010 by the certified third-party supervisor 1121
- EN 13381-8 (ETA 11/0324)
Shelf Life
In unopened original container: 18 months from date of production
Storage Conditions
Storage temperature between +5 °C and +30 °C. Store cool and dry.
Density
~ 1.31 kg/l
Flash Point
+32 °C
Solid content by volume
~ 71 ± 3 % | (BCF Guidance Method) |
Application
Relative Air Humidity
Max. 80 %
Dew Point
No condensation!
The substrate temperature during application and curing must be at least 3 °C above the dew point.
Surface temperature
Min. +5 ° C, max. +40 ° C
For higher temperatures please contact the technical sales adviser.
Waiting Time / Overcoating
Sika® Unitherm® Steel S requires a minimum drying time of 24 hours before the Sika® Unitherm® Top S or Sika®Unitherm® Top W top coat can be applied.
The through-drying of Sika® Unitherm® Steel S can be checked by "fingernail test".
Prior to further applications possible contaminations must be removed.
Drying Time
Touch-dry: | < 1 hour | (+23 °C, 60 % r.h.) |
Overcoatable: | ~ 4 hours with itself | (+23 °C, 60 % r.h.) |
Depending on the total layer thickness of Sika® Unitherm® Steel S.
Deviating temperatures, relative humidities and dry film thicknesses have an influence on the drying time.
Consumption
Fire resistance class F30
Components | Profile | Profile coefficient U/A
| Dry film thickness
| Theoretical material requirement1. g/m2 | Wet layer thickness1.
|
Beams Columns Trusses | Open | < 80 < 100 < 130 < 160 < 180 < 200 < 300 | 200 250 300 350 400 450 500 | 380 470 560 660 750 840 930 | 285 355 425 495 565 635 710 |
Columns Trusses | Closed | < 60 < 80 < 100 < 120 < 140 < 160 < 180 < 200 < 220 < 240 < 265 < 300 | 300 400 500 600 700 800 900 1 000 1 100 1 200 1 300 1 450 | 570 760 940 1 120 1 310 1 490 1 670 1 860 2 040 2 220 2 410 2 690 | 435 580 720 850 1 000 1 140 1 280 1 420 1 570 1 710 1 850 2 060 |
-
Determined reference values
Fire resistance class F60
Components | Profile | Profile coefficient U/A
| Dry film thickness
| Theoretical material requirement1. g/m2 | Wet layer thickness1.
|
Beams Columns Trusses | Open | < 100 < 110 < 120 < 130 < 140 < 150 < 160 < 167 < 174 < 180 < 186 < 193 < 200 < 220 < 240 < 260 < 280 < 300 | 1 100 1 200 1 300 1 400 1 500 1 600 1 700 1 800 1 900 2 000 2 100 2 200 2 300 2 400 2 500 2 600 2 700 2 800 | 2 050 2 230 2 420 2 600 2 780 2 970 3 150 3 340 3 520 3 710 3 890 4 080 4 260 4 440 4 720 4 815 5 000 5 180 | 1 570 1 710 1 850 1 990 2 130 2 270 2 410 2 550 2 680 2 830 2 980 3 120 3 260 3 400 3 610 3 680 3 820 3 960 |
Columns Trusses | Closed | < 100 | 1 900 | 3 520 | 2 680 |
-
Determined reference values
Example
1 000 μm dry correspond to approx. 1 400 μm wet
Reference
The ratio of dry film thickness to wet film thickness depends, among other things, on the respective application method.
The above consumption data correspond to minimum application quantities without bulk and spray loss.
SURFACE PREPARATION
Steel
Blasting in preparation grade Sa 2½ according to EN ISO 12944-4.
Free of dirt, oil, grease and corrosion products.
Steel, hand rusting
Manual derusting (steel brush or suitable tool) in surface preparation degree St 3, EN ISO 12944-4.
Galvanized steel
Free of dirt, oil, grease and corrosion products.
For continuous underwater and condensation water exposure, lightly blast surfaces with a ferrite-free abrasive (sweep blasting according to EN ISO 12944-4).
Existing coating, old coating
Please contact the Technical Department.
MIXING
Stir thoroughly with slowly turning mechanical stirrer, free of lumps.
APPLICATION
The specified dry film thickness is achieved with the airless spraying process. The attainment of a uniform coating thickness and uniform appearance depends on the application method. In general, the spraying process leads to the best result. Depending on the design, the required coating thickness can be achieved by brushing or roller application, further work processes must be planned for local conditions. Before starting the coating work, it is advisable to check by means of a test area on site whether the selected application method with the agreed product corresponds to the requirements in the result.
Painting, rolling
- Lambskin rollers, medium pile, solvent resistant
- Paint brushes, solvent-resistant
Airless spraying
Material: | Process undiluted |
Pump: | Powerful piston pump |
Gear transmission ratio: | 45:1 |
Sieves and filters: | Remove |
Hose diameter: | ≥ NW 10 |
Whip: | 1.5 - 2.0 m, NW 6, possible |
Recommended nozzle diameter: | 0.53 - 0.66 mm or 0.021 - 0.027 inches |
Hoses: | Use only for dispersion! |
Protect the coating from the effects of the weather until the entire coating has been completed and fully cured. Ensure adequate ventilation.
Note: Sika® Unitherm® Steel S must be applied in several coats to the final dry film thickness. The wet layer thickness of the first coat directly onto the primer should be max. 400 μm. A wet coat thickness of approx. 750 μm is recommended for each subsequent coat.
CLEANING OF TOOLS
SikaCor® Cleaner